The Isco Pump Station Monitoring system includes a programmable data logger, data retrieval and communications options, and Pumplink software.
Lift Station flow measurement and pump performance monitoring.
Windows-based software for Pump Station flow and performance monitoring.
Lift Station flow measurement and pump performance monitoring.
The 4501 monitors operation of lift station pumps as the wet well fills and is emptied. Combining this information with the known volume between the levels in the wet well, the 4501 uses patented algorithms (US Patent No. 5,597,960) to calculate the flow into and out of the pump station, and the pumping rate of each pump. Pump activity data is also stored in the 4501’s memory for analysis on a PC with Isco Pumplink™ Software. Standard Features
Applications
Options and Accessories
|
Specifications
4501 Pump Station Monitor |
|
Size (HxWxD): | 3.75 x 3.75 x 7.1 in. (9.5 x 9.5 x 18.1 cm) |
Weight: | 1.4 lbs. (0.63 kg) |
Material: | Polyphenylene oxide |
Enclosure: | Standard ¼ DIN; Portable protective enclosure with carrying handle is optional |
Power: | 12V DC, 250 mA |
Storage Temperature: | -40 to 140°F (-40 to 60°C) |
Operating Temperature: | 0 to 140°F (18 to 60°C) |
Display: | Backlit liquid crystal, 2 lines, 32 characters |
Keypad: | membrane, 4 position |
Data Storage and communication |
|
Capacity: | 29,000 events maximum |
Storage Mode: | Rollover |
Program Memory: | Battery backed RAM; can be updated via interrogator port without opening the enclosure |
Data Retrieval: | Direct RS-232 connection, Optional internal telephone modem |
Data Analysis: | Isco Pumplink Software (compatible with Windows 95, 98, 2000, NT, and XP) |
Flow Measurement Accuracy: | ±1% totalized flow, ±8% cycle to cycle typical (Does not include errors in wetwell measurements. With Pumplink software ±5% cycle to cycle is typical) |
Relay Outputs: | 2 normally open, rated 1A at 30V DC or 0.3 A at 125V AC, one proportional to outflow, one activated based on minimum and maximum analog inputs and abnormal pump capacity |
Pump Inputs: | 3, rated 12 to 120V AC or DC |
Connection: | Anything that turns on or off when the pumps are activated |
Analog Outputs: | 2 proportional to inflow and outflow rates, 4 to 20 mA into a maximum of 400 ohms |
Digital Inputs: | 4, rated 12 to 120V AC or DC |
Analog Inputs: | 8 single-ended mixed with (optional) 4 differential, individually selectable 4 to 20 mA or 0 to 5 V |
Windows-based software for Pump Station flow and performance monitoring.
Pumplink™ Software complements the 4501 Pump Station Monitor. Pumplink sets up the data logging parameters on the 4501, and makes it easy to analyze and store information on pump station flows and pump performance. Standard Features
Applications
|
Specifications
Typical Accuracy (Does not include errors in wetwell measurements) |
|
Pumplink Software: | ±1% totalized flow, ±5% cycle to cycle |